(1)
Except where the wind loads are derived from the combined Cg Cp values determined in accordance with Article 4.1.7.6., buildings and structural members shall be capable of withstanding the effects of the following loads:
(a)
the full wind loads acting along each of the 2 principal horizontal axes considered separately,
(b)
75% of the wind loads described in Clause (a) but offset from the central geometric axis of the building by 15% of its width normal to the direction of the force to produce the worst load effect,
(c)
75% of the wind loads described in Clause (a) but with both axes considered simultaneously, and
(d)
56% of the wind loads described in Clause (a) but with both axes considered simultaneously and offset from the central geometric axis of the building by 15% of its width normal to the direction of the force. (See Note A-4.1.7.9.(1))