(1)
In a dwelling unit, a warm-air supply outlet shall be provided in each finished room that is located adjacent to unheated space.
(2)
Except as provided in Sentence (3), when a room described in Sentence (1) is located adjacent to exterior walls, such outlet shall be located so as to bathe at least one exterior wall or window with warm air, except in bathrooms, utility rooms or kitchens, where this may not be practical.
(3)
Where the heating system is also designed to provide ventilation air, ceiling outlets or outlets located high on interior walls are permitted to be installed, provided the outlets are designed for this purpose and are installed with diffusers.
(4)
At least one warm-air supply outlet shall be provided for each 40 m
(5)
At least one warm-air supply outlet shall be provided for each 80 m
(6)
Except for pipeless furnaces and floor furnaces, the capacity of warm-air supply outlets serving dwelling units shall be not less than the design heat loss from the area served and shall not exceed 3 kW per outlet.
(7)
In basements and heated crawl spaces, the calculated heat gain from the supply ducts and plenum surfaces is permitted to be considered in calculating the design heat loss.
(8)
The temperature of supply air at warm-air supply outlets shall not exceed 70°C.
(9)
Warm-air supply outlets located in finished areas shall be provided with diffusers and adjustable openings and shall not be located on a furnace plenum.
(10)
Air duct systems serving storage garages shall not be interconnected with other parts of the building.