(See Note A-9.32.3.10.)

(1)

Except as provided in Sentence (4), capacity ratings for required fans shall be determined in accordance with

(a)

CAN/CSA-C260-M, “Rating the Performance of Residential Mechanical Ventilating Equipment,” or

(b)

HVI Publication 916, “Airflow Test Procedure.”

(2)

Sound ratings for fans shall be determined in accordance with

(a)

CAN/CSA-C260-M, “Rating the Performance of Residential Mechanical Ventilating Equipment,” or

(b)

HVI Publication 915, “Loudness Testing and Rating Procedure.”

(3)

Capacity ratings for fans shall be measured at the external static pressure differentials shown in Table 9.32.3.10.-A.

Table 9.32.3.10.-A Minimum External Static Pressure Differential for Rating of Fans

Forming Part of Sentence 9.32.3.10.(3)

(4)

Fans in heat recovery ventilators used to provide one or more required fans shall have their airflow at normal temperature rated in accordance with CAN/CSA-C439, “Standard laboratory methods of test for rating the performance of heat/energy-recovery ventilators.”

(5)

Where a heat recovery ventilator is used to provide one or more required fans, it shall have a low-temperature ventilation reduction factor of not less than 50% when tested in accordance with CAN/CSA-C439, “Standard laboratory methods of test for rating the performance of heat/energy-recovery ventilators,” at an outdoor temperature at least as low as the outdoor design temperature for the location where the ventilation system is to be installed, but the outdoor design temperature need not be lower than -25°C.

(6)

Fans, including make-up air supply fans, installed to satisfy Articles 9.32.3.3. to 9.32.3.8. with less than 1 m of duct between themselves and the visible interior surfaces of rooms other than unfinished basements, furnace rooms, utility rooms and attics, shall have a sound rating complying with Table 9.32.3.10.-B when operating at the required flow rate.

(7)

Mechanical ventilation devices shall conform to CSA C22.2 No. 113, “Fans and Ventilators.”

Table 9.32.3.10.-B Maximum Sound Rating for Fans

Forming Part of Sentence 9.32.3.10.(6)