(1)

Floor joists supported on the side of flat insulating concrete form walls shall be supported with joist hangers secured to wood ledger boards.

(2)

The ledger boards referred to in Sentence (1) shall be not less than

(a)

38 mm thick, and

(b)

the depth of the floor joists.

(3)

Anchor bolts shall be used to secure ledger boards to flat insulating concrete form walls and shall be

(a)

embedded in the wall to a depth not less than 100 mm, and

(b)

spaced in accordance with Table 9.20.17.5.

(4)

Floor joists and building frames supported on the top of flat insulating concrete form walls shall be anchored in conformance with Article 9.23.6.1.

Table 9.20.17.5. Maximum Anchor Bolt Spacing for the Connection of Floor Ledgers to Flat Insulating Concrete Form Walls