(1)

Only crawl spaces under 1- storey portions of dwelling units shall be used as warm air plenums.

(2)

Enclosing material in crawl spaces described in Sentence (1), including insulation, shall have a surface flame-spread rating not greater than 150.

(3)

Combustible ground cover used as enclosing material in Sentence (2) shall be covered with noncombustible material. (See Note A-9.18.7.1.(3) and (4))

(4)

Noncombustible material described in Sentence (3) shall

(a)

extend not less than 300 mm beyond the projection of a register opening, and

(b)

have turned-up edges. (See Note A-9.18.7.1.(3) and (4))