(1)
Reserved.
(2)
Except as provided in Sentence (5), a fire alarm system shall be installed
(a)
in every building that contains more than 3 storeys, including storeys below the first storey,
(b)
where the total occupant load exceeds 300, or
(c)
when the occupant load for any major occupancy in Table 9.10.18.2. is exceeded.
(3)
Reserved.
(4)
Reserved.
(5)
A fire alarm system is not required in a residential occupancy where an exit or public corridor serves not more than 4 suites or where each suite has direct access to an exterior exit facility leading to ground level.
Table 9.10.18.2. Maximum Occupant Load for Buildings Without Fire Alarm Systems
Forming Part of Sentence 9.10.18.2.(2)