(1)
The effective area of the surface of the filter medium in each filter bed shall be at least 10 m
(2)
The area described in Sentence 8.7.4.2.(1) shall be designed such that the loading rate does not exceed, for soil having a percolation time set out in Column 1 of Table 8.7.4.1., the maximum value set out opposite it in Column 2 of Table 8.7.4.1.
(3)
Except as provided in Sentence (5), where the total daily design sanitary sewage flow does not exceed 3 000 L, the effective area shall be such that the loading on the surface of the filter medium does not exceed 75 L/m
(4)
Except as provided in Sentence (5), where the total daily design sanitary sewage flow exceeds 3 000 L
(a)
the effective area shall be such that the loading on the surface of the filter medium does not exceed 50 L/m
(b)
the leaching bed shall be comprised of more than one filter bed, each of similar size and adjacent to each other.
(5)
Where a Level II, Level III or Level IV treatment unit as described in Table 8.6.2.2. is used in conjunction with a filter bed, the effective area shall be such that the loading on the surface of the filter medium does not exceed 100 L/m