(1)

Except as provided in Sentence (2), every stack that drains fixtures from more than 4 storeys containing plumbing fixtures shall have a vent stack.

(2)

A stack that serves as a wet vent does not require a vent stack.

(3)

The vent stack required by Sentence (1) shall be connected to a vertical section of the stack at or immediately below the lowest sanitary drainage pipe connected to the stack.

(4)

Fixtures are permitted to be connected to a vent stack, provided

(a)

the total hydraulic load of the connected fixtures does not exceed 8 fixture units,

(b)

at least one fixture is connected to a vertical portion of the vent stack and upstream of any other fixtures,

(c)

no other fixture is connected downstream of a water closet,

(d)

all fixtures are located in the lowest storey served by the vent stack, and

(e)

the section of the vent pipe that acts as a wet vent conforms to the requirements regarding wet vents.