(1)

Except as provided for in Sentence (2), traps shall

(a)

have a trap seal depth of not less than 38 mm,

(b)

be so designed that failure of the seal walls will cause exterior leakage, and

(c)

have a water seal that does not depend on the action of moving parts. (See Note A-7.2.3.1.(1) and (3))

(2)

The trap seal depth on fixtures draining to an acid waste system shall be a minimum of 50 mm.

(3)

Except for a floor-mounted service sink, every trap that serves a lavatory, a sink or a laundry tray shall

(a)

be provided with a cleanout plug located at the lowest point of the trap and of the same material as the trap, except that a cast iron trap shall be provided with a brass cleanout plug, or

(b)

be designed so that part of the trap can be removed for cleaning purposes. (See Note A-7.2.3.1.(1) and (3))

(4)

A bell trap shall not be installed in a drainage system.

(5)

A drum trap shall not be installed in a drainage system.

(6)

Except as permitted in Sentence (7), no bottle trap shall be used in a plumbing system.

(7)

A bottle trap may be used on a laboratory sink or other fixture equipped with corrosion resistant fittings.

(8)

No running trap shall be installed in a plumbing system unless an accessible handhole is provided for cleaning of the trap, and where the trap is too small to accommodate a handhole, a cleanout shall be provided.