(See Note A-4.1.5.8.)
(1)
One- and two-way floor slabs shall have no reduction for tributary area applied to live load.
(2)
An area used for assembly occupancies designed for a live load of less than 4.8 kPa and roofs designed for the minimum loading specified in Table 4.1.5.3. shall have no reduction for tributary area.
(3)
Where a structural member supports a tributary area of a floor or a roof, or a combination thereof, that is greater than 80 m
(4)
Where a structural member supports a tributary area of a floor or a roof, or a combination thereof, that is greater than 20 m
(5)
Where the specified live load for a floor is reduced in accordance with Sentence (3) or (4), the structural drawings shall indicate that a live load reduction factor for tributary area has been applied and which structural elements are impacted by this factor.