(1)

Where one or more water-bottle filling stations are provided at each location, at least one shall be equipped with controls that

(a)

activate automatically, or

(b)

comply with Clause 3.8.1.5.(1)(c).

(2)

Water-bottle filling stations required by Sentence (1) that are located in a storey where a barrier-free path of travel is required shall

(a)

be located along the barrier-free path of travel,

(b)

have a clear floor space of 800 mm by 1 350 mm in front of them, (See Note A-3.8.3.16A.(2)(b))

(c)

where they have frontal access, provide a knee clearance in accordance with Clause 3.8.3.11.(1)(c),

(d)

be operable at a height of not more than 1 200 mm above the floor, and (See Note A-3.8.3.16A.(2)(d))

(e)

be equipped with controls that

(i)

activate automatically, or

(ii)

comply with Sentence 3.8.1.5.(1). (See Sentences 3.3.1.8.(2) and (3) on horizontal projections.)