(See Note A-3.8.2.2.)

(1)

A direct barrier-free path of travel shall be provided between a barrier-free entrance referred to in Article 3.8.1.2. to

(a)

a designated barrier-free parking area, where provided,

(b)

an exterior passenger-loading zone, where provided, and

(c)

a public thoroughfare. (See Note A-3.8.2.2.(1) and (4))

(2)

The vehicular entrance to and egress from any parking level described in Sentence (1) and all areas intended to be used by wheelchair accessible vehicles to gain access to a parking space on that level shall have a vertical clearance of not less than 2 100 mm.

(3)

If an exterior passenger loading zone is provided, it shall have

(a)

an access aisle not less than 2 440 mm wide and 7 400 mm long adjacent and parallel to the vehicle pull-up space,

(b)

a curb ramp, where there are curbs between the access aisle and the vehicle pull-up space, and

(c)

a clearance height of not less than 3 600 mm at the vehicle pull-up space and along the vehicle access and egress routes.

(4)

In storage garages, a barrier-free path of travel shall be provided between each parking level with barrier-free parking and all other parts of the building required to be provided with barrier-free access that are served by that storage garage. (See Note A-3.8.2.2.(1) and (4))