(1)
If access is provided through a fire separation between a storage garage and a Group A, Division 1 or Group B occupancy or a retirement home, the access shall be through a vestibule conforming to Sentence (4).
(2)
Reserved.
(3)
In a building more than 3 storeys in building height, access through a fire separation between a storage garage and a Group A, Division 2, 3 or 4, or a Group C occupancy, shall be through a vestibule conforming to Sentence (4).
(4)
If access is provided through a vestibule, as required by Sentences (1), (3) and 3.3.5.4.(1), the vestibule shall
(a)
be not less than 1.8 m long,
(b)
be ventilated
(i)
naturally to outside air by a vent that has an unobstructed area of not less than 0.1 m
(ii)
mechanically at a rate of 14 m
(c)
have openings between the vestibule and an adjoining occupancy provided with self-closing doors with no hold-open devices.