(1)
A corridor used by the public or serving patients or residents shall have no dead-end portion unless the area served by the dead-end portion has a second and separate means of egress.
(2)
A corridor serving patients in a hospital shall be not less than 2 400 mm wide.
(3)
Except as permitted in Sentence (5), a corridor serving residents who are not ambulatory in a Group B, Division 2 or 3 occupancy shall be not less than 1 650 mm wide.
(4)
Paired doors in a corridor serving patients or residents shall
(a)
swing in opposite directions, the right hand door swinging in the direction of travel, and
(b)
be not less than 1 100 mm wide.
(5)
A corridor in a Group B, Division 3 occupancy that contains sleeping accommodation for not more than 10 persons and not more than 6 occupants require assistance in evacuation in case of an emergency need not comply with Sentence (3).