3.2.3.5. Wall With Limiting Distance Less Than 1.2 m

Feb 03, 2026© King's PrinterJan 16, 2025

(1)

Openings in a wall that has a limiting distance less than 1.2 m shall be protected by closures whose fire-protection rating is in conformance with the fire-resistance rating required for the wall.

(2)

Wired glass or glass block shall not be used for a closure referred to in Sentence (1).