(1)
A building classified as Group F, Division 2 is permitted to conform to Sentence (2) provided
(a)
except as permitted by Sentences 3.2.2.7.(1) and 3.2.2.18.(2), the building is sprinklered throughout,
(b)
it is not more than 4 storeys in building height, and
(c)
it has a building area not more than
(i)
18 000 m
(ii)
9 000 m
(iii)
6 000 m
(iv)
4 500 m
(2)
Except as permitted by Article 3.2.2.16., the building referred to in Sentence (1) shall be of noncombustible construction, and
(a)
floor assemblies shall be fire separations with a fire-resistance rating not less than 1 h,
(b)
mezzanines shall have a fire-resistance rating not less than 1 h, and
(c)
loadbearing walls, columns and arches shall have a fire-resistance rating not less than that required for the supported assembly.