(1)
A building classified as Group B, Division 3 is permitted to conform to Sentence (2) provided
(a)
except as permitted by Sentences 3.2.2.7.(1) and 3.2.2.18.(2), the building is sprinklered throughout,
(b)
it is not more than 3 storeys in building height, and
(c)
it has a building area
(i)
that is not limited if the building is not more than 1 storey in building height,
(ii)
not more than 12 000 m
(iii)
not more than 8 000 m
(2)
Except as permitted by Article 3.2.2.16., the building referred to in Sentence (1) shall be of noncombustible construction, and
(a)
floor assemblies shall be fire separations with a fire-resistance rating not less than 1 h,
(b)
mezzanines shall have a fire-resistance rating not less than 1 h, and
(c)
loadbearing walls, columns and arches shall have a fire-resistance rating not less than that required for the supported assembly.