(1)

Except as permitted by Sentences (2) and (3), a building classified as Group A, Division 4 shall be of noncombustible construction.

(2)

Roof assemblies and supporting arches and columns are permitted to be of heavy timber construction.

(3)

A building classified as Group A, Division 4 is permitted to be of combustible construction provided

(a)

the occupant load is less than 1 500, and

(b)

the building has a limiting distance not less than 6 m.

(4)

Sprinklers shall be installed in all spaces below tiers of seats in a building classified as Group A, Division 4 if those spaces are used for occupancy. (See Note A-3.2.2.35.(4))