(1)
A building classified as Group A, Division 3 is permitted to conform to Sentence (2) provided
(a)
except as permitted by Sentences 3.2.2.7.(1) and 3.2.2.18.(2), the building shall be sprinklered throughout,
(b)
it is not more than 2 storeys in building height, and
(c)
it has a building area not more than
(i)
12 000 m
(ii)
6 000 m
(2)
Except as permitted by Clause (c) and Article 3.2.2.16., the building referred to in Sentence (1) shall be of noncombustible construction, and
(a)
floor assemblies shall be fire separations with a fire-resistance rating not less than 1 h,
(b)
mezzanines shall have a fire-resistance rating not less than 1 h, and
(c)
loadbearing walls, columns and arches shall have a fire-resistance rating not less than that required for the supported assembly, except that arches are permitted to be of heavy timber construction.