3.2.1.5. Fire Containment in Basements

Feb 03, 2026© King's PrinterJan 16, 2025

(1)

Except as permitted by Sentences (2) and 3.2.2.15.(3), in a building in which an automatic sprinkler system is not required to be installed by Articles 3.2.2.18., every basement shall

(a)

be sprinklered throughout, or

(b)

be subdivided into fire compartments not more than 600 m2 in area by a fire separation having a fire-resistance rating not less than that required for the floor assembly immediately above the basement.

(2)

An open-air storey need not conform to Sentence (1).