(See Note A-3.1.9.3.) (See also Note A-3.1.9.2.(1))

(1)

Except as provided in Sentence (3), outlet boxes are permitted to penetrate the membrane of an assembly required to have a fire-resistance rating, provided they are sealed at the penetration by a firestop that has an FT rating not less than the fire-resistance rating of the fire separation when subjected to the fire test method in CAN/ULC-S115, “Standard Method of Fire Tests of Firestop Systems.”

(2)

Combustible outlet boxes are permitted to penetrate the membrane of an assembly required to have a fire-resistance rating, provided they are sealed at the penetration by a firestop that, when subjected to the fire test method in CAN/ULC-S115, “Standard Method of Fire Tests of Firestop Systems,” has an FT rating not less than the fire-resistance rating for the fire separation.

(3)

Except as provided in Sentences 3.1.9.1.(2) and (3), noncombustible outlet boxes that penetrate a vertical fire separation or a membrane forming part of an assembly required to have a fire-resistance rating need not conform to Sentence (1), provided

(a)

they do not exceed,

(i)

0.016 m² in area, and

(ii)

an aggregate area of 0.065 m² in any 9.3 m² of surface area, and

(b)

the annular space between the membrane and noncombustible electrical outlet boxes does not exceed 3 mm.

(4)

Outlet boxes on opposite sides of a vertical fire separation having a fire-resistance rating shall be separated by

(a)

a horizontal distance of not less than 600 mm,

(b)

a fire block conforming to Article 3.1.11.7., or

(c)

a firestop installed on each outlet box that has an FT rating not less than the fire-resistance rating of the fire separation when subjected to the fire test method in CAN/ULC-S115, “Standard Method of Fire Tests of Firestop Systems.”