(1)

A door assembly having a fire-protection rating not less than 20 min is permitted to be used as a closure in

(a)

a fire separation not required to have a fire-resistance rating more than 1 h, located between

(i)

a public corridor and a suite,

(ii)

a corridor and adjacent sleeping rooms, or

(iii)

a corridor and adjacent classrooms, offices and libraries in Group A, Division 2 major occupancies, or

(b)

a fire separation not required to have a fire-resistance rating more than 45 min, located in a building not more than 3 storeys in building height.

(2)

The requirements for noncombustible sills and combustible floor coverings in NFPA 80, “Standard for Fire Doors and Other Opening Protectives,” do not apply to a door described in Sentence (1).

(3)

A door described in Sentence (1) shall have clearances of not more than 6 mm at the bottom and not more than 3 mm at the sides and top.

(4)

In elementary and secondary schools, a door assembly conforming to Articles 9.10.13.2. and 9.10.13.3. is permitted to be used as a closure in a fire separation having a fire-resistance rating of 30 min.