(1)
Except for crawl spaces conforming to Sentence 3.1.11.6.(1) and as required in Sentence (3), horizontal concealed spaces within a floor assembly or roof assembly of combustible construction, in which sprinklers are not installed, shall be separated by construction conforming to Article 3.1.11.7. into compartments
(a)
not more than 600 m
(b)
not more than 300 m
(2)
A concealed space in an exterior cornice, a mansard style roof, a balcony or a canopy in which exposed construction materials within the space have a flame-spread rating more than 25, shall be separated by construction conforming to Article 3.1.11.7.
(a)
at locations where the concealed space extends across the ends of required vertical fire separations, and
(b)
so that the maximum dimension in the concealed space is not more than 20 m.
(3)
Except as provided by Sentence (5), in buildings or parts thereof conforming to Article 3.2.2.51. or 3.2.2.60., horizontal concealed spaces within a floor assembly or roof assembly of combustible construction shall be separated by construction conforming to Article 3.1.11.7. into compartments that are
(a)
not more than 600 m
(b)
not more than 300 m
(4)
Except for crawl spaces conforming to Sentence 3.1.11.6.(1) and except as provided in Sentence (5), in buildings or parts thereof conforming to Article 3.2.2.48., 3.2.2.57. or 3.2.2.93., horizontal concealed spaces within a floor assembly or roof assembly of encapsulated mass timber construction shall be separated by construction conforming to Article 3.1.11.7. into compartments that are
(a)
not more than 600 m
(b)
not more than 300 m
(5)
Fire blocks conforming to Sentences (3) and (4) are not required where the horizontal concealed space within the floor or roof assembly is entirely filled with noncombustible insulation such that any air gap between the top of the insulation and the floor or roof deck does not exceed 50 mm.