(1)
Except as provided by Sentences (2) and (3), every floor area shall be served by at least 2 exits.
(2)
A floor area classified as a Group G, Division 1 major occupancy is permitted to be served by a single exit, provided the floor area is not more than
(a)
10 m
(b)
20 m
(3)
A floor area classified as a Group G, Division 2 or 3 major occupancy is permitted to be served by a single exit, provided the floor area is not more than
(a)
200 m
(b)
300 m