(1)

Except as permitted by Sentence (2) and required by Sentence (3), fuel-fired appliances shall be installed in service rooms separated from the remainder of the farm building by

(a)

a fire separation having a fire-resistance rating not less than 45 min in a floor area that is not sprinklered throughout, or

(b)

a fire separation not required to have a fire-resistance rating in a floor area that is sprinklered throughout.

(2)

A fuel-fired appliance that serves only one room is not required to be installed in a service room separated from the remainder of the farm building.

(3)

Incinerators shall be installed in service rooms that

(a)

do not contain other fuel-fired appliances, and

(b)

are separated from the remainder of the farm building by a fire separation having a fire-resistance rating not less than

(i)

2 h, where the service room is adjacent to a Group G, Division 1 major occupancy in a floor area that is not sprinklered throughout,

(ii)

1 h, where the service room is adjacent to a Group G, Division 1 major occupancy in a floor area that is sprinklered throughout,

(iii)

1 h, where the service room is adjacent to a Group G, Division 2 or 3 major occupancy in a floor area that is not sprinklered throughout, or

(iv)

30 min, where the service room is adjacent to a Group G, Division 2 or 3 major occupancy in a floor area that is sprinklered throughout.

(4)

A room containing a device that produces open flames, heat or sparks and used for crop drying shall be separated from the remainder of the farm building by

(a)

a fire separation having a fire-resistance rating not less than 45 min in a floor area that is not sprinklered throughout, or

(b)

a fire separation not required to have a fire-resistance rating in a floor area that is sprinklered throughout.

(5)

A room intended to be used for repairing farm machinery shall be separated from the remainder of the farm building by a fire separation having a fire-resistance rating not less than

(a)

1 h, in a floor area that is not sprinklered throughout, or

(b)

30 min, in a floor area that is sprinklered throughout.

(6)

Storage areas for dangerous goods shall be separated from the remainder of the farm building in accordance with Sentences 3.3.6.2.(1) and (2).