Distance between classrooms: 6 m or more 3.2.2. applies to each classroom 3.2.3. does not apply between classrooms Extinguisher required Access; street; hydrant; fire alarm; - not required

Distance between classrooms: less than 6 m 3.2.2. applies to each classroom 3.2.3. applies to each classroom i.e. rating and construction of facing walls determined by limiting distance Extinguisher required Access; street; hydrant; fire alarm; - not required

Distance between classrooms: less than 6 m No. of classrooms in group: 6 max.

Distance between groups: not less than 12 m 3.2.2. applies to each group 3.2.3. does not apply between classrooms within a group if the facing walls have a rating of 45 min, on the inside 3.2.3. applies between groups Extinguisher required Access; street; hydrant; fire alarm - not required

Distance between classrooms: less than 6 m No. of classrooms in group: 6 max.

Distance between groups: not less than 12 m 3.2.2. applies to each group 3.2.3. does not apply between classrooms within a group 3.2.3. applies between groups Extinguisher required Fire alarm required (extension of main system) Access; street; hydrant; - not required

Distance between classrooms: less than 6 m No. of classrooms in group: 6 max.

Distance between groups: not less than 12 m 3.2.2. applies to each group 3.2.3. does not apply between classrooms within a group 3.2.3. applies between groups Extinguisher required Fire alarm required (extension of main system) Access; street; hydrant; - not required All other cases require: - Fire extinguisher - Access - Street - Hydrant - Fire alarm: extension of existing system