(1)

Aspects of mechanical ventilation systems not specifically described in this Subsection shall be designed, constructed and installed in accordance with good practice such as that described in the ASHRAE Handbooks and Standards, the HRAI Digest, the HRAI Residential Mechanical Ventilation Manual, the Hydronics Institute Manuals and the SMACNA Manuals.

(2)

Ventilation system equipment installed to meet the requirements of this Section shall be installed in accordance with the manufacturers’ instructions and recommendations except that, where such instructions and recommendations are in conflict with the requirements of this Subsection, the requirements of this Subsection shall govern.

(3)

Except where mounted on concrete foundations, fans and heat recovery ventilators shall be isolated from structural components by resilient mountings to minimize the transmission of noise and vibration to occupied spaces.

(4)

Where flow-regulating dampers are required,

(a)

they shall be adjustable and accessible without requiring the removal of fans, motors or insulating materials, or the use of specialized tools, and

(b)

a device on the outside of the duct or device in which they are installed shall indicate the position of the damper.

(5)

Ventilation equipment shall be accessible for inspection, maintenance, repair and cleaning.

(6)

Ventilation equipment installed in unheated spaces shall be installed so as to avoid condensation of moisture on fans and motors, in accordance with the manufacturers’ instructions.