(1)
Flashing beneath weep holes in cavity walls and masonry veneer/masonry backing walls shall
(a)
be bedded not less than 25 mm in the inside wythe,
(b)
extend to not less than 5 mm beyond the outer face of the building element below the flashing, and
(c)
be installed with a nominally horizontal slope toward the outside wythe.