Hyperlinked
Ontario Building Code

◉

❯

Volume 1

❯

Division B

❯

Part 9

9.10.13.8. Maximum Size of Opening

Feb 03, 2026© King's PrinterJan 16, 2025

(1)

The size of an opening in an interior fire separation, even where protected with a closure, shall not exceed 11 m², with no dimension greater than 3.7 m, if a fire compartment on either side of the fire separation is not sprinklered.

(2)

The size of an opening in an interior fire separation, even where protected with a closure, shall not exceed 22 m², with no dimension greater than 6 m, when the fire compartments on both sides of the fire separation are sprinklered.

  • (1)
  • (2)