(See Note A-8.4.1.2.)

(1)

A Class 2 sewage system shall be designed only for the treatment and disposal of greywater.

(2)

The total daily design flow for a Class 2 sewage system shall be calculated based on the fixtures discharging to the system as follows:

(a)

200 L per fixture unit where there is a supply of pressurized water, and

(b)

125 L per fixture unit where there is no supply of pressurized water.