7.4.9.5. Offset in Leaders

Feb 03, 2026© King's PrinterJan 16, 2025

(1)

No change in the nominal pipe size of a leader with a nominally horizontal offset is required if the offset

(a)

is located immediately under the roof,

(b)

is not more than 6 m long, and

(c)

has a slope of not less than 1 in 50.

(2)

If the horizontal offset is more than 6 m long, the leader shall conform to Table 7.4.10.9.