(1)

Cleanouts and access covers shall be located so that their openings are readily accessible for drain cleaning purposes.

(2)

A cleanout shall not be

(a)

located in a floor assembly in a manner that may constitute a hazard, and

(b)

used as a floor drain.

(3)

Reserved.

(4)

Each change of direction of the piping between a cleanout fitting and the drainage piping or vent piping that it serves shall be accomplished by using 45 ° bends.

(4.1)

A cleanout shall be provided to serve vertical drainage piping from a wall hung urinal and shall extend above the flood level rim of the fixture.

(5)

Cleanouts serving fixture drains in healthcare facilities, mortuaries, laboratories and similar occupancies, where contamination by hazardous waste is likely, shall be located a minimum of 150 mm above the flood level rim of the fixture.