(1)

Where a storm drainage system is connected to a combined building sewer or a public combined sewer, a trap shall be installed between any opening in the system and the drain or sewer, except that no trap is required if the opening is the upper end of a leader that terminates

(a)

at a roof that is used only for weather protection,

(b)

not less than 1 m above or not less than 3.5 m in any other direction from any air inlet, openable window or door, and

(c)

not less than 1.8 m from a property line. (See Note A-7.4.5.2.(1))

(2)

A floor drain that drains to a storm drainage system shall be protected by a trap that

(a)

is located between the floor drain and a leader, storm building drain or storm building sewer,

(b)

may serve all floor drains located in the same room, and

(c)

need not be protected by a vent pipe.