(1)

Two or more fixture outlet pipes that serve outlets from a single fixture that is listed in Clause 7.4.2.1.(1)(d) may be directly connected to a branch that

(a)

has a nominal pipe size of not less than NPS 1¼, and

(b)

is terminated above the flood level rim of a directly connected fixture with a minimum diameter waste of 1½ in. to form an air break.

(2)

Fixture drains from fixtures that are listed in Subclauses 7.4.2.1.(1)(e)(i) and (ii) may be directly connected to a pipe that

(a)

is terminated to form an air break above the flood level rim of a fixture that is directly connected to a sanitary drainage system, and

(b)

is extended through the roof when fixtures that are on 3 or more storeys are connected to it.

(3)

Fixture drains from fixtures that are listed in Subclauses 7.4.2.1.(1)(d)(iii) to (vi) may be directly connected to a pipe that,

(a)

is terminated to form an air break above the flood level rim of a fixture that is directly connected to a storm drainage system, and

(b)

is extended through the roof when fixtures that are on 3 or more storeys are connected to it.

(4)

Every waste pipe carrying waste from a device for the display, storage, preparation or processing of food or drink shall be trapped and have a minimum diameter equal to the diameter of the drain outlet from the device.