(1)
Where a water pressure test is made, all air shall be expelled from the system before fixture control valves or faucets are closed.
(2)
Potable water shall be used to test a potable water system.
Where a water pressure test is made, all air shall be expelled from the system before fixture control valves or faucets are closed.
Potable water shall be used to test a potable water system.