(1)
A Group A, Division 4 occupancy and each tier or balcony that has a capacity of more than
(a)
1 000 persons shall have no fewer than three separate exits, or
(b)
4 000 persons shall have no fewer than four separate exits.
(2)
In a Group A, Division 4 occupancy, every seat shall be located so that the travel distance is not more than 45 m measured along the path of travel from the seat to
(a)
the ground,
(b)
an exit,
(c)
an opening to a passageway leading from the seating area, or
(d)
a portal, a vomitory or any other opening through the seating deck structure.
(3)
Exits from outdoor stadia or grandstands shall be located not more than 25 m apart.
(4)
The capacity of a means of egress for a Group A, Division 4 occupancy shall conform to the requirements of Sentence 3.4.3.2.(3).
(5)
Aisles in a Group A, Division 4 occupancy shall
(a)
be located so that there are not more than 20 seats between any seat and the nearest aisle, and
(b)
be not less than 1 200 mm wide, except that an aisle serving less than 60 persons is permitted to be 750 mm wide.