3.2.8.8. Combustible Content Limits

Feb 03, 2026© King's PrinterJan 16, 2025

(1)

An interconnected floor space shall be designed so that the combustible contents, excluding interior finishes, in those parts of a floor area in which the ceiling is more than 8 m above the floor, are limited to not more than 16 g of combustible material for each cubic metre of volume of the interconnected floor space.