(1)

A building containing an interconnected floor space shall be sprinklered throughout.

(2)

Except for large floor openings as defined in NFPA 13, “Standard for the Installation of Sprinkler Systems,” closely spaced sprinklers and associated draft stops shall be installed around floor openings in conformance with NFPA 13.