(1)
An exposing building face in a storage garage with all storeys constructed as open-air storeys is permitted to have unlimited unprotected openings provided it has a limiting distance not less than 3 m.
(2)
The exposing building face of a storey that faces a street and is at the same level as the street is permitted to have unlimited unprotected openings if the limiting distance is not less than 9 m.