3.2.2.33. Group A, Division 3, One Storey, Sprinklered

Feb 03, 2026© King's PrinterJan 16, 2025

(1)

A building classified as Group A, Division 3 is permitted to be of combustible construction or noncombustible construction used singly or in combination, provided,

(a)

except as permitted by Sentences 3.2.2.7.(1) and 3.2.2.18.(2), the building is sprinklered throughout,

(b)

it is not more than 1 storey in building height, and

(c)

it has a building area not more than 7 200 m2.