(1)

Where a fire alarm system is required by Sentence 2.2.3.1.(1),

(a)

the air-handling system, where provided, shall be designed to prevent the circulation of smoke upon a signal from a duct-type smoke detector if the air-handling system serves more than 1 storey, and

(b)

a manual station shall be installed in every floor area near every exit.